UPS SYSTEM ONELINE DRAWING

091505

A

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

OUTPUT TO CRITICAL
LOAD

BATTERY CABINET

BATTERY
BREAKER

E4. E5

E9
E10
E11
E12

FUSE

K5

STATIC
SWITCH

FUSE

K3

FUSE

BATTERY CON­
VERTER

RECTIFIER

INVERTER

K1

UPM 1

E1
E2
E3

E6
E7
E8
E12

A

B

SEE NOTE 2

MODULE TIE
CABINET (OP­
TIONAL)

D

MOB 1

F

E

BATTERY CABINET

BATTERY
BREAKER

E4. E5

E9
E10
E11
E12

FUSE

K5

STATIC
SWITCH

FUSE

K3

FUSE

BATTERY CON­
VERTER

RECTIFIER

INVERTER

K1

UPM 2

E1
E2
E3

E6
E7
E8
E12

A

B

SEE NOTE 2

D

MOB 2

MIS

MBP

TYPICAL PARALLEL SYSTEM

(1+1 AND 2+0 CONFIGURATIONS)

*

*

*

*

3 of 5

C

C

164201603-4

G

NOTE

1. UPM and system bypass input feeds
must come from the same source.

2. Remove jumper for dual‐feed.

3. See Note 28 on page A-27 for
neutral bonding instructions.

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-8

A -

AC Input to UPS Rectifier (dual‐feed)

B -

AC Input to UPS Rectifier (single‐feed) and Bypass (single‐feed and dual‐feed)

C -

DC Input from Battery

D -

UPM AC Output to Parallel Tie Point

E -

AC Input Source

F -

System Bypass Input

G -

Output to Critical Load

* -

Overcurrent Protection Provided by Others