INSTALLING A REMOTE EMERGENCY POWER-OFF CONTROL

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

5-2

NOTE REPO switch rating is 6A/120 Vac or 3A/240 Vac. The REPO switch must be a latching-type switch
with a dedicated circuit.

REPO

Switch

Twisted Wires (2)

4

5

CUSTTB

Figure 5‐2. REPO Wiring

5.

If you are installing multiple REPO stations, wire additional stations in parallel
with the first REPO station.

6.

If required, install ½” conduit and wiring from the second contact block in the
REPO station to trip circuitry of other equipment, such as upstream protective
devices, facility monitoring devices, or alarms. Using the contact block that was
not used for the UPS EPO wiring will help maintain isolation between the control
systems.

A normally‐open (NO) contact and a normally‐closed (NC) contact are provided,
and the two are electrically isolated. If single-pole, double-throw action is desired,
one side of the NO contact can be jumpered to one side of the NC contact to
form the common connection point. REPO switch wiring must be according to
UL Class I requirements.

7.

Secure the UPS by reversing all steps taken to prepare it for a REPO station
installation.