Powerware 9390 UPS 100160 kVA User Manual

Page 190

Advertising
background image

1 of 15

INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS

032406

B

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

164201603-8

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-42

1.

Use Class 1 wiring methods (as defined by the NEC) for power wiring.

2.

Use Class 2 wiring methods (as defined by the NEC) for interface wiring from 30 to 600V.

3.

When installing external interface wiring (for example, building alarm, relay output, battery
breaker trip, and X-Slot) to the UPS interface terminals, conduit must be installed
between each device and the UPS cabinet. Install the interface wiring in separate conduit
from the power wiring.

4.

When installing internal interface wiring to X-Slot terminals, route the wiring through the
internal opening in the X-Slot communication bay.

5.

All building alarm inputs or remote features require an isolated normally‐open contact or
switch (rated at 24 Vdc, 20 mA minimum) connected between the alarm input and
common terminal as shown. All control wiring and relay and switch contacts are
customer‐supplied. Use twisted‐pair wires for each alarm input and common.

6.

The building alarms can be programmed to display the alarm functional name.

7.

See Table W through Table AC and Chapters 4, 5, and 6 for customer interface wiring.

8.

LAN and telephone drops for use with X-Slot connectivity cards must be provided by
facility planners or the customer.

Table W. TB1 and TB2 Interface Connections

Terminal TB1

Name

Description

1

Remote EPO NC

Input: Normally‐closed dry contact to activate EPO of UPS
from a remote switch

2

Remote EPO Return

3

Remote EPO NO

Input: Normally‐open dry contact to activate EPO of UPS
from a remote switch

4

Remote EPO Return

5

Batt Breaker Aux

Input: Normally‐open contact to indicate when UPS UVR
battery breaker is open.

6

Batt Breaker Aux Return

7

Battery UVR (+)

Output: Fused 48 Vdc source to control operation of Battery
Breaker UVR function.

8

Battery UVR (-)

9

Building Alarm 1

Input: Programmable UPS alarm, activated by a remote dry
contact closure.

10

Building Alarm 1 Return

Terminal TB2

Name

Description

1

Building Alarm 2

Input: Programmable UPS alarm, activated by a remote dry
contact closure. Dedicated for Pull Chain function when part
of Parallel System.

2

Building Alarm 2 Return

3

On Bypass NO

Output: Normally‐open contact closes when UPS is on
bypass. Dedicated for Pull Chain function when part of
Parallel System.

4

On Bypass Common

5

Alarm Relay NC

Output: General purpose normally‐closed relay contact.

6

Alarm Relay Common

7

Alarm Relay NO

Output: General purpose normally‐open relay contact.

8

Alarm Relay Common

9

On Inverter NC

Output: Normally‐closed contact opens when output
contactor closes.

10

On Inverter Common

NOTE: “RETURN“ INDICATES CONNECTION TO ELECTRONICS CIRCUIT GROUND. “COMMON” INDICATES CONNECTION
TO COMMON SIDE OF ISOLATED RELAY CONTACT.