DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS

5 of 15

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-46

9.

The UPS DC UVR trip and Battery Aux signal wiring from the UPS must be connected to
the DC source disconnect device.

10.

Battery Aux and UVR wiring should be a minimum of 18 AWG.

Table X. Battery Disconnect Interface

BATTERY AUX +

BATTERY

BREAKER OR

DISCONNECT

6

7

8

TB1

5

BATTERY AUX -

BATTERY UVR +

BATTERY UVR -

UPS

Table Y. Alarm Relay Contact

7

5

6

ALARM RELAY

TB2

8

UPS

CONTACT RATING

Switched Voltage:

277 Vac

28 Vdc

Maximum Current: 5A

Minimum Wire Size: 22 AWG

NOTE:

Relays are shown in de‐energized state. Relays change state when the

UPS is in Normal mode.