Powerware hot sync can bridge card – Powerware 9390 UPS 100160 kVA User Manual

Page 198

Advertising
background image

091505

A

164201603-8

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS

POWERWARE HOT SYNC CAN BRIDGE CARD

CONNECTIONS FOR PARALLEL SYSTEM CONTROL

CONNECTIONS FOR RMP, RIM, OR SCM
(ONLY ONE DEVICE CAN BE CONNECTED AT A TIME)

BUILDING ALARM 2 REPLACEMENT

J3

NOTE

All interface wiring is to be
provided by the customer.

9 of 15

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-50

16.

Conduit must be installed between the UPM cabinets for parallel interface wiring. Install the
interface wiring in separate conduit from the power wiring.

17.

Use Class 1 wiring methods (as defined by the NEC) for parallel interface wiring. The wire
should be shielded twisted pair, rated for 5 amps maximum.

18.

See Table AC and Chapter 6 for parallel interface wiring.

Table AC. Powerware Hot Sync

®

CAN Bridge Card Interface Connections

Terminal J3

Name

Description

1

Alarm

Programmable UPS alarm. Activated by a remote
dry contact closure.

2

Alarm Rtn

3

Not Used

Not Used

4

Not Used

Not Used

5

Not Used

Not Used

6

TX

Remote Monitor Panel (RMP), Relay Interface
Module (RIM), or Supervisory Contact Module
(SCM) connections.

7

TX

8

CAN L

Computer Area Network (CAN) Input for parallel
operation.

9

CAN H

10

Shield