Bypass mode – parallel, 3 bypass mode – parallel – Powerware 9390 UPS 100160 kVA User Manual

Page 62

Advertising
background image

UNDERSTANDING UPS OPERATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

7-10

7.2.3

Bypass Mode – Parallel

In Bypass mode, the output of the system is provided with three-phase AC power
directly from the bypass input. While in this mode, the output of the system is not
protected from fluctuations, spikes, or power outages from the source. No power
filtering, conditioning, or battery support is available to the output of the system in the
Bypass mode of operation.

The parallel system automatically switches to Bypass mode if it detects a UPM
overload, UPMs unavailable, load fault, or internal failure.

Figure 7‐6 shows the path of electrical power through the parallel system when
operating in Bypass mode.

Main Power Flow

UPM 1

UPM 2

UPM 3

UPM 4

Output to

Critical

Load

Battery

UPM Input

Module Tie Cabinet

UPM 1 Output

Bypass Input

UPM 2 Output

UPM 3 Output

UPM 4 Output

Battery

Battery

Battery

Closed

Open

Breakers

Figure 7‐6. Path of Current through the UPMs in Bypass Mode – Parallel

In a parallel redundant or capacity type system, each module operates similar to a
single module, but in parallel with each other. The bypass source for the load is
derived from the bypass input of one, two, three, or four modules, depending on the
system configuration through the internal continuous-duty static switches. If a module
is taken offline, the other modules remain online to support the load. If more modules
than can support the load must be taken offline, the load must be transferred to
maintenance bypass or shut down.

Advertising