POWER WIRING INSTALLATION NOTES

B

110106

12 of 23

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

164201603-5

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-22

Table N. Power Cable Conduit Requirements (Cont'd)

UPS Model

Voltage

Terminal

Number of

Wires in
Conduit

Minimum Conduit

Trade Size (inches)

Number of

Conduits

Powerware

9390-80/60

208/220

AC

AC Input to UPS

(A, B, C, Gnd)

4

2‐1/2

1

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

2‐1/2

1

Output

(A, B, C, Neut, Gnd)

5

2‐1/2

1

DC

Battery

(Positive), (Negative), Gnd

3

1‐1/2

1

Powerware

9390-80/60

380/
415/

480

AC

AC Input to UPS

(A, B, C, Gnd)

4

2

1

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

2

1

Output

(A, B, C, Neut, Gnd)

5

2

1

DC

Battery

(Positive), (Negative), Gnd

3

1‐1/2

1

Powerware

9390-80/80

208/220

AC

AC Input to UPS

(A, B, C, Gnd)

4

2‐1/2

2

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

2‐1/2

2

Output

(A, B, C, Neut, Gnd)

5

2‐1/2

2

DC

Battery

(Positive), (Negative), Gnd

3

2

1

Powerware

9390-80/80

380/
415/

480

AC

AC Input to UPS

(A, B, C, Gnd)

4

2‐1/2

1

AC Input to Bypass

(A, B, C, Neut, Gnd)

5

2‐1/2

1

Output

(A, B, C, Neut, Gnd)

5

2‐1/2

1

DC

Battery

(Positive), (Negative), Gnd

3

2

1