background image

RTN

BUILDING ALARM #1 INPUT

NOTE 1. All building alarm inputs require an isolated normally‐open or

normally‐closed contact or switch (rated at 24 Vdc, 20 mA minimum)
connected between the alarm input and common terminal as shown.
Building alarm inputs can be programmed for use with either normally‐open
or normally‐closed contacts. All control wiring and relay and switch contacts
are customer‐supplied.

2. The building alarms can be programmed to display the alarm functional
name.

3. A jumper wire must be connected between pins 1 and 2 on TB1, if the
normally‐closed EPO contact is not used.

032406

B

164201603-8

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS

INTERFACE TERMINALS

1

10

1

10

TB1

TB2

BUILDING ALARM
RTN

PARALLEL PULL CHAIN INPUT-BLDG ALARM #2

ALARM RELAY
NC

ALARM RELAY RTN

ALARM RELAY
NO

REMOTE EPO: NO

REMOTE EPO: NC
EPO RTN

BATTERY BRKR AUX CONTACT +

BATTERY BRKR AUX RETURN -

BATTERY BRKR UVR (+48V FUSED)

BATTERY BRKR UVR CONTROL(-)

UPS

ON BYPASS NO

ON BYPASS COMMON

ON INVERTER (K3 AUX) : NC

ON INVERTER (K3 AUX) : COMMON

3 of 15

EPO RTN

ALARM RELAY RTN

JUMPER REQUIRED
IF NOT USED

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com