UNDERSTANDING UPS OPERATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

7-9

7.2.2

Normal Mode – Parallel

In Normal mode, utility AC power is supplied to the UPMs. Each UPM then conditions
the incoming AC power and provides clean, regulated AC power to either a module
tie cabinet or distribution panel for parallel systems up to four modules. The applied
load is equally shared among the available UPMs in the system.

Figure 7‐5 shows the path of electrical power through the parallel system when
operating in Normal mode.

Main Power Flow

UPM 1

UPM 2

UPM 3

UPM 4

Output to

Critical

Load

Battery

UPM Input

Module Tie Cabinet

UPM 1 Output

Bypass Input

UPM 2 Output

UPM 3 Output

UPM 4 Output

Battery

Battery

Battery

Closed

Open

Breakers

Figure 7‐5. Path of Current through the UPMs in Normal Mode – Parallel

If the utility AC power is interrupted or is out of specification, the UPMs automatically
switch to Battery mode to support the critical load without interruption. When utility
power returns, the UPMs return to Normal mode.

If the UPMs become overloaded or unavailable, the parallel system switches to
Bypass mode. The parallel system automatically returns to Normal mode when the
overload condition is cleared and system operation is restored within specified limits.