POWER WIRING INSTALLATION NOTES

071608

C

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

164201603-5

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-13

Table G. INPUT/OUTPUT Ratings & External Wiring Requirements for the Powerware 9390-40/40 and
9390-80/40

Units

Rating 50/60 Hz

Basic Unit Rating at 0.9 lagging pF
load

kVA

kW

40
36

40
36

40
36

40
36

40
36

Input and Bypass Input
Output

VOLTS
VOLTS

208/220
208/220

380
380

400
400

415
415

480
480

AC Input to UPS Rectifier
(0.98 min. pF)
Full Load Current plus Battery
Recharge Current
(3) Phases, (1) Ground

A

Amps

125

68

64

63

55

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

2/0

(1)

2

(1)

2

(1)

2

(1)

4

(1)

AC Input to UPS Bypass
Full Load Current
(3) Phases, (1) Neutral-if required,
(1) Ground

B

Amps

111/105

61

58

56

48

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

2/0

(1)

2

(1)

2

(1)

2

(1)

4

(1)

DC Input from Battery to UPS
(1) Positive, (1) Negative

C

Vdc

Amps@

(2.0V/cell)

384-480

101

432-480

101

432-480

101

432-480

101

432-480

101

Minimum Conductor Size
Number per Pole

AWG or kcmil

(each)

1/0

(1)

1/0

(1)

1/0

(1)

1/0

(1)

1/0

(1)

AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral-if required, (1)
Ground

D

Amps

111/105

61

58

56

48

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

2/0

(1)

2

(1)

2

(1)

2

(1)

4

(1)

Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 7)

-

AWG or kcmil

(each)

4

(1)

6

(1)

6

(1)

6

(1)

6

(1)

NOTE Callout letters

A

,

B

,

C

, and

D

map to Drawing 164201603-4, sheets 1 of 5,

3 of 5, 4 of 5, and 5 of 5.

C

A

U

T

I

O

N

DELTA SOURCES (TN‐S) - The Powerware 9390 UPS system can be operated only from a delta supply source that is fully
floating and if the neutral‐forming transformer kit (PN 103005400) is installed in the UPS. The UPS cannot be operated from a
mid‐point or end‐point grounded delta supply source. With this type of supply source, there is no capability to provide an
output neutral. In no circumstances shall a neutral to ground bonding jumper be installed in the UPS.

8.

The UPS cabinet is shipped with a debris shield covering the ventilation grill on top of the
unit. Do not remove the debris shield until installation is complete. However, remove the
shield before operating the UPS. Once the debris shield is removed, do not place objects
on the ventilation grill.