POWER WIRING INSTALLATION NOTES

071608

D

6 of 23

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

164201603-5

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-16

Table J. INPUT/OUTPUT Ratings & External Wiring Requirements for the Powerware 9390-80/80

Units

Rating 50/60 Hz

Basic Unit Rating at 0.9 lagging pF load

kVA

kW

80
72

80
72

80
72

80
72

80
72

Input and Bypass Input
Output

VOLTS
VOLTS

208/220
208/220

380
380

400
400

415
415

480
480

AC Input to UPS Rectifier
(0.98 min. pF)
Full Load Current plus Battery
Recharge Current
(3) Phases, (1) Ground

A

Amps

240

135

130

125

105

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

2/0

(2)

2/0

(1)

2/0

(1)

2/0

(1)

1/0

(1)

AC Input to UPS Bypass
Full Load Current
(3) Phases, (1) Neutral-if required,
(1) Ground

B

Amps

222/210

122

116

111

96

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

2/0

(2)

2/0

(1)

2/0

(1)

2/0

(1)

1/0

(1)

DC Input from Battery to UPS
(1) Positive, (1) Negative

C

Vdc

Amps@

(2.0V/cell)

384-480

203

432-480

203

432-480

203

432-480

203

432-480

203

Minimum Conductor Size
Number per Pole

AWG or kcmil

(each)

3/0

(1)

3/0

(1)

3/0

(1)

3/0

(1)

3/0

(1)

AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral-if required, (1)
Ground

D

Amps

222/210

122

116

111

96

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

2/0

(2)

2/0

(1)

2/0

(1)

2/0

(1)

1/0

(1)

Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 7)

-

AWG or kcmil

(each)

1/0

(1)

6

(1)

6

(1)

6

(1)

6

(1)

NOTE Callout letters

A

,

B

,

C

, and

D

map to Drawing 164201603-4, sheets 1 of 5,

3 of 5, 4 of 5, and 5 of 5.