Parallel system can (pull chain) wiring, Parallel system can wiring – Powerware 9390 UPS 100160 kVA User Manual

Page 199

Advertising
background image

091505

A

164201603-8

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS

NOTE

This drawing is for parallel wiring purposes and is not a floor layout plan.
UPMs can be placed in any physical order.

PARALLEL SYSTEM CAN (PULL CHAIN) WIRING

UPM

1

UPM

2

UPM

3

UPM

4

CAN

(IF INSTALLED)

(IF INSTALLED)

PULL CHAIN

PARALLEL SYSTEM CAN WIRING

10 of 15

TWISTED PAIR

TWISTED PAIR

TWISTED PAIR

UPM 1

CAN CARD J3

UPM 2

CAN CARD J3

UPM 3

CAN CARD J3

(IF INSTALLED)

UPM 4

CAN CARD J3

(IF INSTALLED)

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-51

CAN Wiring Terminations

From UPM 1 CAN Card

To UPM 2 CAN Card

To UPM 3 CAN Card

(If Installed)

To UPM 4 CAN Card

(If Installed)

J3–8 (L)

J3–8 (L)

J3–8 (L)

J3–8 (L)

J3–9 (H)

J3–9 (H)

J3–9 (H)

J3–9 (H)

J3–10 (Shield)

J3–10 (Shield)

J3–10 (Shield)

J3–10 (Shield)