Relay interface module, Figure 10‐2. relay interface module – Powerware 9390 UPS 100160 kVA User Manual

Page 123

Advertising
background image

USING FEATURES AND OPTIONS

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

10-3

The RMP contains a local horn and the backlit status indicators listed in Table 10‐1.

Table 10‐1. RMP Status Indicators

SYSTEM NORMAL

The UPS is energized (either with utility power or battery backup) and is
supplying conditioned power to the critical load.

NO REDUNDANCY

This indicator applies only to parallel systems when one cabinet is not
functioning.

ON GENERATOR

The UPS input and bypass are being supplied by the power from the genera­
tor instead of from the utility power.

ON BYPASS

The bypass source is supplying the critical load. Usually this means that
the UPS is not energized. The load is not protected in Bypass mode, and a
horn sounds after 30 seconds.

UPS ALARM

The UPS system is issuing an alarm. Conditions that affect the current
UPS mode are indicated by the indicators and horn on the UPS.

ON BATTERY

The UPS battery backup is supplying the critical load. The utility power is
either interrupted or out of specification. The SYSTEM NORMAL indicator
is also illuminated.

BYPASS UNAVAILABLE

The UPS system is in Normal mode, but a bypass source is not within
specification. A horn sounds after 30 seconds.

SHUTDOWN IMMINENT

The UPS is preparing to shut down because the UPS is in Battery mode
and the DC voltage is approaching its low limit. This indicator is
accompanied by a horn.

Advertising