POWER WIRING INSTALLATION NOTES

110106

B

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

UPM 2

Battery

Bypass inputs to UPMs

UPM 1

Battery

UPM 3

Battery

UPM 4

Battery

Outputs from UPMs

1A

2A

3A

4A

1B

2B

3B

4B

23 of 23

164201603-5

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-33

33.

Required parallel system wiring length should be in accordance with the following rule, as
referenced to the diagram below, to ensure approximately equal current sharing when in
Static Bypass mode:

(Total length of 1A + 1B)

 (Total length of 2A + 2B)  (Total length of 3A + 3B) (Total length of 4A + 4B)

This rule has a tolerance of approximately

10% for the combined input and output wire

lengths.

If installing only two UPMs in a fully redundant system, this requirement is no longer
required, as each UPM is capable of supporting the full bypass requirement. However, this
would preclude future expansion.