Powerware 9390 UPS 100160 kVA User Manual

Page 151

Advertising
background image

164201603-2

1 of 2

PHYSICAL FEATURES AND REQUIREMENTS

071608

C

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-3

1.

The UPS equipment operating environment must meet the weight requirements shown in
Table A and the size requirements shown on Drawing 164201603-9.

2.

The UPS cabinet is palleted separately for shipping.

3.

Do not tilt cabinets more than

"

10° during handling.

4.

Dimensions are in millimeters (inches).

5.

The cabinet can be installed in line‐up‐and‐match or standalone configurations.

Table A. UPS Cabinet Weight

Model

Voltage

Weight

kg (lb)

Input

Output

Shipping

Installed

Point Loading

Powerware 9390-40/20

208V/220V

208V/220V

231 (508)

208 (458)

4 at 52.2 (115)

380V/400V/

415V/480V

380V/400V/

415V/480V

Powerware 9390-40/30

208V/220V

208V/220V

231 (508)

208 (458)

4 at 52.2 (115)

380V/400V/

415V/480V

380V/400V/

415V/480V

Powerware 9390-40/40

208V/220V

208V/220V

231 (508)

208 (458)

4 at 52.2 (115)

380V/400V/

415V/480V

380V/400V/

415V/480V

Powerware 9390-80/40

208V/220V

208V/220V

313 (690)

290 (640)

4 at 72.5 (160)

380V/400V/

415V/480V

380V/400V/

415V/480V

271 (618)

258 (568)

4 at 64.5 (142)

Powerware 9390-80/50

208V/220V

208V/220V

313 (690)

290 (640)

4 at 72.5 (160)

380V/400V/

415V/480V

380V/400V/

415V/480V

271 (618)

258 (568)

4 at 64.5 (142)

Powerware 9390-80/60

208V/220V

208V/220V

313 (690)

290 (640)

4 at 72.5 (160)

380V/400V/

415V/480V

380V/400V/

415V/480V

271 (618)

258 (568)

4 at 64.5 (142)

Powerware 9390-80/80

208V/220V

208V/220V

313 (690)

290 (640)

4 at 72.5 (160)

380V/400V/

415V/480V

380V/400V/

415V/480V

271 (618)

258 (568)

4 at 64.5 (142)

Advertising