INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-54

Parallel Interface Wire Charts Using Customer–Supplied MOB Dual Aux Contacts

Building Alarm Pull Chain Wiring Terminations All Modules

From UPM 1

To UPM 2

To UPM 3

To UPM 4

Function

Remarks

CAN Card
J3-10

CAN Card
J3-10

CAN Card
J3-10

CAN Card
J3-10

External CAN

Network

Shielded

Twisted Pair

CAN Card
J3-9

CAN Card
J3-9

CAN Card
J3-9

CAN Card
J3-9

CAN Card
J3-8

CAN Card
J3-8

CAN Card
J3-8

CAN Card
J3-8

TB2-2

TB2-4

TB2-4

TB2-4

Pullchain

From UPM 1

To MOB 1

Function

Remarks

CAN Card J3-1

AUX 1: NC

MOB Open Alarm

Twisted Pair

CAN Card J3-2

AUX 1: COM

TB2-1

AUX 2: NO

Pullchain

From UPM 2

To MOB 2

Function

Remarks

CAN Card J3-1

AUX 1: NC

MOB Open Alarm

Twisted Pair

CAN Card J3-2

AUX 1: COM

TB2-1

AUX 2: NO

Pullchain

From UPM 3

To MOB 3

Function

Remarks

CAN Card J3-1

AUX 1: NC

MOB Open Alarm

Twisted Pair

CAN Card J3-2

AUX 1: COM

TB2-1

AUX 2: NO

Pullchain

From UPM 4

To MOB 4

Function

Remarks

CAN Card J3-1

AUX 1: NC

MOB Open Alarm

Twisted Pair

CAN Card J3-2

AUX 1: COM

TB2-1

AUX 2: NO

Pullchain

From MOB 1

To MOB 2

To MOB 3

To MOB 4

Remarks

AUX 2: COM

AUX 2: COM

AUX 2: COM

AUX 2: COM

Pullchain MOB

Common

Bypass Relay Pull Chain Jumpers

All UPMs

Jumper From

To

TB2–1 (Building Alarm 2)

TB2–3 (Bypass)

TB2–2 (Building Alarm 2 Rtn)

TB2–4 (Bypass Rtn)

071608

A

164201603-8

INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

PARALLEL SYSTEM BACKUP

CONTROL (PULL CHAIN) WIRING

FOR CUSTOMER–SUPPLIED

TIE PANEL

13 of 15

NOTE

1.

Valid only for TB1 & TB2 with +48V fuseholder configuration.

2.

NC and NO designation on MOB AUX contacts are defined with breaker in OFF (open) position.

3.

If MOB contacts have flying leads, use the same wire gauge to connect to UPS and use the
correct crimp connections for the wire gauge.

4.

Use twisted pair wiring between module and MOB AUX contacts.

5.

Always confirm contact operation prior to wiring.

6.

External CAN connections on CAN bridge terminals require shielded twisted pair wire between
modules.