RESPONDING TO SYSTEM EVENTS

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

11-5

Table 11‐2. Notices

Message

Horn

Phone

Relay

Log*

Indication

Automatic Shutdown Pending

1

No

No

A

Information Only

Automatic Shutdown Pending OK

OFF

No

No

A

Condition Cleared

Automatic Startup Pending

1

No

No

A

Information Only

Battery Current Limit

1

No

No

HA

Information Only

Battery Current Limit OK

Off

No

No

HA

Condition Cleared

Battery Voltage High

1

1

No

HA

Information Only

Battery Voltage High OK

Off

No

No

HA

Condition Cleared

Battery Voltage Low

1

No

No

HA

Information Only

Battery Voltage Low OK

Off

No

No

HA

Condition Cleared

Bypass AC Over Voltage

1

No

No

HA

Information Only

Bypass AC Over Voltage OK

Off

No

No

HA

Condition Cleared

Bypass AC Under Voltage

1

No

No

HA

Information Only

Bypass AC Under Voltage OK

Off

No

No

HA

Condition Cleared

Bypass Phase Rotation

1

No

No

HA

Information Only

Bypass Phase Rotation OK

Off

No

No

A

Condition Cleared

Bypass Source Out of Tolerance

1

No

No

HA

Investigate UPS

Bypass Source Out of Tolerance OK

Off

No

No

HA

Condition Cleared

Bypass Under or Over Frequency

1

No

No

HA

Information Only

Bypass Under or Over Frequency OK

Off

No

No

HA

Condition Cleared

Charger Off Command

1

No

No

HA

Information Only

Charger On Command

1

No

No

HA

Information Only

Charger Over Voltage or Current

1

No

No

HA

Information Only

Charger Tripped

1

No

No

HA

Information Only

Charger Tripped OK

Off

No

No

HA

Condition Cleared

Check Battery

1

No

No

HA

Information Only

Check Battery OK

Off

No

No

HA

Condition Cleared

Check Modem

1

No

No

HA

Information Only

Check Modem OK

Off

No

No

HA

Condition Cleared

DC Link Over Voltage

1

1

No

HA

Information Only

DC Link Over Voltage OK

Off

No

No

A

Condition Cleared

DC Link Under Voltage

1

No

No

HA

Information Only

DC Link Under Voltage OK

Off

No

No

HA

Condition Cleared

Emergency Transfer To Bypass

1

No

No

HA

Information Only

Emergency Transfer To Bypass OK

Off

No

No

A

Condition Cleared

* Log codes indicate where the UPS records the event: H = History log, HA = History and Active logs, and A = Active log only.