INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS

6 of 15

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS (20–80 kVA) Installation and Operation Manual

S 164201603 Rev 2 www.powerware.com

A-47

11.

The Remote EPO feature opens all contactors in the UPS cabinet and isolates power from
your critical load. Local electrical codes may also require tripping upstream protective
devices to the UPS. The REPO switch must be a latching‐type switch with a dedicated
circuit.

12.

A jumper wire must be connected between pins 1 and 2 on TB1, if a normally‐closed EPO
switch is not used or a normally‐open EPO switch is used.

13.

Remote EPO wiring should be a minimum of 22 AWG.

Table Z. Remote EPO

1 (NC)

4 (RETURN)

TWISTED

WIRES

UPS TB1

REMOTE

EPO

SWITCH

REMOTE

EPO

SWITCH

2 (RETURN)

3 (NO)

(NC TYPE)

(NO TYPE)

TWISTED

WIRES

OR

LATCHING‐TYPE

SWITCH ONLY

INSTALL

JUMPER IF

SWITCH NOT

INSTALLED

THIS POSITION

SWITCH ONLY

LATCHING‐TYPE

Remote EPO switch rating is 24 Vdc, 1A minimum.

NOTE:

The REPO switch must be a latching‐type switch with a

dedicated circuit.