IDEC SmartRelay functions

124

IDEC SmartRelay Manual

resumes operation until the time-to-go has expired, for

example.

To enable this response, however, the relevant functions

must be set retentive. Two options are available:
R : The data is retained.
/ : Current data is not retained (default). See the example on

Page 90.

SFs operating hours counter, seven-day time switch, twelve-

month time switch and PI controller are always retentive.

4.3.5

Parameter protection

In the parameter protection settings, you can determine

whether or not the parameters can be displayed and edited

in IDEC SmartRelay parameter assignment mode. Two

options are available:
+ : The parameter attribute permits read/write access in

parameter assignment mode (default).

- : The parameter settings are read-/write-protected in

parameter assignment mode, and can be edited only in

programming mode. See the example on Page 90.

Note

Parameter protection covers only the "Set Param" window. If you
embed variables of protected special functions in a message text,
the variables are still editable from the message text. To protect
these variables, also activate the protection of the message text.