Example 6: Yearly mode off, Monthly mode off, Pulse

selected, On Time = 2008

03

15, Off Time = ****

**

**: On

March 15, 2008 the timer output switches on for one cycle.

Because the timer does not have a monthly action or yearly

action, the timer output pulses only one time at the specified

On Time.

B6 2+
ON :
YYYY–MM–DD
2008–03–15

B6 1+
Yearly =Off
Monthly=Off
Pulse =On

B6 3+
OFF :
YYYY–MM–DD
****–**–**

Example 7: Yearly mode on, Monthly mode off, Pulse off,

On Time = 2008

12

15, Off Time = 2010

01

07: On

December 15 of 2008 and 2009, the timer output switches on

and remains on until January 7 of the following year. When

the timer output turns off on January 7, 2010 it does NOT

turn on again the following December 15.

B6 2+
ON :
YYYY–MM–DD
2008–12–15

B6 1+
Yearly = On
Monthly=Off
Pulse =Off

B6 3+
OFF :
YYYY–MM–DD
2010–01–07