IDEC SmartRelay functions

IDEC SmartRelay Manual

147

Timing diagram

Functional description

A 0 to 1 signal transition at input Trg sets output Q. The next

1 to 0 transition at Trg retriggers the current time T

a

, and

output Q remains set.
Output Q is reset when T

a

= T. You can output a warning

signal before the off-delay time (T - T

!

) has expired to reset

Q for the time of the pre-warning period T

!L

.

A further one-shot at input Trg during T

a

retriggers the time

T

a

.

If retentivity is not set, output Q and the expired time are

reset after a power failure.

Setting the Par parameter

Note the defaults specified in Chapter 4.3.2.

Note

All times must have the same timebase.

View in programming mode (example):

B9 1+R
T

=60:00s

Protection mode and retentivity
Off-delay time

Press

B9 2
T!

=05:00s

T!L =00:10s

Start of the off-warning period

(T - T!)

Off-warning time