A.10 technical data: fl1b-j2b2, Technical data – IDEC FL1E SmartRelay User Manual

Page 332

Advertising
background image

Technical data

318

IDEC SmartRelay Manual

A.10 Technical data: FL1B-J2B2

FL1B-J2B2

Power supply
Input voltage

12/24 V DC

Permissible range

10.8 ... 28.8 V DC

Power consumption

25 ... 50 mA

Voltage failure buffering

typ. 5 ms

Power loss at
• 12 V
• 24 V

0.3 ... 0.6 W
0.6 ... 1.2 W

Electrical isolation

No

Reverse polarity protection

Yes

Ground terminal

for connecting ground and shielding of the
analog measuring line

Analog inputs
Number

2

Type

Unipolar

Input range

0 ... 10 V DC (input impedance 76 k

) or 

0 ... 20 mA (input impedance <250

)

Resolution

10 bit, normalized to 0 ... 1000

Cycle time for analog value generation

50 ms

Electrical isolation

No

Line length (shielded and twisted)

10 m

Encoder supply voltage

none

Error limit

+/- 1.5 %

Interference frequency suppression

55 Hz

Advertising