Connecting IDEC SmartRelay inputs

Requirements

At the inputs you connect sensor elements such as:

momentary pushbuttons, switches, light barriers, daylight

control switches etc.

Sensor characteristics for IDEC SmartRelay

(1): 1.0 mA (Version 1 to 5 specifications)
(2): 8 V DC (Version 1 to 5 specifications)
(3): 1.0 mA (Version 1 to 4 specifications)
(4): 8 V DC (Version 1 to 4 specifications)
(5): 1.5 mA (Version 1 to 4 specifications)

Note

The digital inputs of FL1E-H12RCC/FL1E-B12RCC are divided into
two groups, each consisting of four inputs. Within the same group,
all inputs must be operated on the same phase. Different phases
are only possible between the groups.
Example: I1 to I4 on phase L1, I5 to I8 on phase L2.
Inputs within the FL1B-M08C2R2 may not be connected to
different phases.

FL1E-H12RCE/

FL1E-B12RCE

FL1E-H12SND

FL1B-

M08B2R2

FL1B-

M08B1S2

I3 ... I6

I1,I2,I7,I8

I3 ... I6

I1,I2,I7,I8

I1 ... I8

I1 ... I8

Signal status 0 < 5 V DC < 5 V DC < 5 V DC < 5 V DC < 5 V DC < 5 V DC
Input current

< 0.85 mA < 0.05 mA < 0.85 mA < 0.05 mA < 0.85 mA

(1)

< 0.85 mA

(3)

Signal status 1 > 8.5 V DC > 8.5 V DC > 12 V DC > 12 V DC > 8.5 V DC

(2)

> 12 V DC

(4)

Input current

> 1.5 mA

> 0.1 mA

> 2 mA

> 0.15 mA

> 1.5 mA

> 2 mA

(5)

FL1E-H12RCA/

FL1E-B12RCA

FL1B-

M08D2R2 (AC)

FL1E-H12RCA/

FL1E-B12RCA

FL1B-

M08D2R2 (DC)

FL1E-H12RCC/

FL1E-B12RCC

FL1B-

M08C2R2 (AC)

FL1E-H12RCC/

FL1E-B12RCC

FL1B-

M08C2R2 (AC)

Signal status 0
Input current

< 5 V AC
< 1.0 mA

< 5 V DC

< 1.0 mA

< 40 V AC

< 0.03 mA

< 30 V DC

< 0.03 mA

Signal status 1
Input current

> 12 V AC

> 2.5 mA

> 12 V DC

> 2.5 mA

> 79 V AC
> 0.08 mA

> 79 V DC

> 0.08 mA