Requirements for a control system of a service
water pump

• Service water must be available at all times. In case of

emergency, the control system must automatically switch

over to drinking water supply.

• When switching over to the drinking water supply, the

ingress of rainwater into the drinking water system must

be prevented.

• The service water pump may not be switched on if the

reservoir has run low of rainwater (dry-run protection).

8.7.2

Previous solution

K1

K2

K3

S1

K3

S4

K3

L1

N

K4

S3

K4

p<

K2

S3

S2

Y1

Auxiliary circuit

Pump

Tracking
time

Dry-run

protection

Drinking water
supply line

The pump and a solenoid valve are controlled by means of a

pressure switch and 3 float switches, which are installed in

the rainwater reservoir. The pump must be switched on

when the pressure level in the boiler drops below minimum.

After the operating pressure is reached, the pump is

switched off again after a tracking time of a few seconds has

expired. The tracking time prevents oscillation of the water

pump if water is drawn off over a longer period of time.