Mathematical rule

Actual value Ax =

(internal value at input Ax • gain) + offset

Gain and offset calculation

The gain and offset is calculated based on the relevant high

and low values of the function.
Example 1:
The available thermocouples have the following technical

data: -30 to +70

C, 0 to 10 V DC (i.e. 0 to 1000 in IDEC

SmartRelay).
Actual value = (internal value • gain) + offset, thus
-30

= (0 • A) + B, i.e. offset B = -30

+70

= (1000 • A) -30, i.e. gain A = 0.1

Example 2:
A pressure sensor converts a pressure of 1000 mbar into a

voltage of 0 V, and a pressure of 5000 mbar into a voltage of

10 V.
Actual value = (internal value • gain) + offset, thus
1000

= (0 • A) + B, i.e. offset B = 1000

5000

= (1000 • A) +1000, i.e. gain A = 4