IDEC SmartRelay functions

IDEC SmartRelay Manual

141

Parameters TH and TL

Note the information on parameter T in Chapter 4.3.2.
The pulse width TH and the interpulse width TL can be

provided by the actual value of another already-programmed

function. You can use the actual values of the following

functions:
• Analog comparator (actual value Ax - Ay, see Chapter

4.4.18)

• Analog trigger (actual value Ax, see Chapter 4.4.16)
• Analog amplifier (actual value Ax, see Chapter 4.4.20)
• Analog multiplexer (actual value AQ, see Chapter 4.4.26)
• Analog ramp control (actual value AQ, see Chapter

4.4.27)

• Analog math (actual value AQ, see Chapter 4.4.30)
• PI controller (actual value AQ, see Chapter 4.4.28)
• Up/down counter (actual value Cnt, see Chapter 4.4.13)
Select the required function by the block number. The

timebase is configurable. For information on valid ranges

and parameter defaults, refer to Chapter 4.4.1.

Trg

T

a

is running

Q

T

H

T

H

N=1
T

L

=0

The bold section of the

timing diagram also

appears in the symbol of

the edge-triggered

interval time-delay relay.

Trg

N=2

Q

T

L

T

H

T

L

T

H

T

L

T

H

T

L

T

H

Timing diagram for the sample

configuration

Timing diagram A

Timing diagram B

Functional description

A 0 to 1 transition at input Trg triggers the time T

L

(Time

Low). After the time T

L

has expired, output Q is set for the

duration of T

H

(Time High).

If there is a further 0 to 1 transition (retriggering pulse) at

input Trg before the preset time (T

L

+ T

H

) has expired, T

a

is

reset and the pulse/pause cycle is restarted.
If retentivity is not set, output Q and the time are reset after

a power failure.