8 random generator, Random generator – IDEC FL1E SmartRelay User Manual

Page 158

Advertising
background image

IDEC SmartRelay functions

144

IDEC SmartRelay Manual

4.4.8

Random generator

Short description

The output of the random generator is set or reset within a

configured time.

Parameter T

H

and T

L

Note the defaults of the T

H

and T

L

parameters listed in

Chapter 4.3.2.
The on-delay time TH and the off-delay time TL can be

provided by the actual value of another already-programmed

function. You can use the actual values of the following

functions:
• Analog comparator (actual value Ax - Ay, see Chapter

4.4.18)

• Analog trigger (actual value Ax, see Chapter 4.4.16)
• Analog amplifier (actual value Ax, see Chapter 4.4.20)
• Analog multiplexer (actual value AQ, see Chapter 4.4.26)
• Analog ramp control (actual value AQ, see Chapter

4.4.27)

• Analog math (actual value AQ, see Chapter 4.4.30)
• PI controller (actual value AQ, see Chapter 4.4.28)
• Up/down counter (actual value Cnt, see Chapter 4.4.13)
Select the required function by the block number. The

timebase is configurable. For information on valid ranges

and parameter defaults, refer to Chapter 4.4.1.

Symbol in IDEC

SmartRelay

Wiring

Description

Input En

A positive edge ( 0 to 1 transition) at
input En (Enable) triggers the on-
delay time of the random generator.
A negative edge ( 1 to 0 transition) at
input En (Enable) triggers the off-
delay time of the random generator.

Parameter

The on-delay is set at random to a
value between 0 s and T

H

.

The off-delay is set at random to a
value between 0 s and T

L

.

Output Q

Output Q is set when the on-delay
has expired and if En is still set. It is
reset when the off-delay has expired,
provided En was not set again
meanwhile.