7 asynchronous pulse generator, Asynchronous pulse generator, B25 2 n =1 – IDEC FL1E SmartRelay User Manual

Page 156

Advertising
background image

IDEC SmartRelay functions

142

IDEC SmartRelay Manual

Setting the Par parameter

View in programming mode (example):

B25 1+R
TL

=02:00s

TH

=03:00s

Protection mode and retentivity
Interpulse width
Pulse width

Press

B25 2
N

=1

Number of pulse/pause cycles

(example)

View in parameter assignment mode (example):

B25
TL =02:00s
TH =03:00s
Ta =01:15s

Current pulse width TL or TH

4.4.7

Asynchronous pulse generator

Short description

The output pulse shape can be modified by reconfiguring the

pulse/pause ratio.

Symbol in IDEC

SmartRelay

Wiring

Description

Input En

You can use input EN to set and reset
the asynchronous pulse generator.

Input INV

Input INV can be used to invert the
output signal of the active
asynchronous pulse generator.

Parameter You can configure the pulse width T

H

and the interpulse width T

L

.

Retentivity:

/ = No retentivity

R = The status is retentive.

Output Q

Q is set and reset cyclically according
to the pulse/pause ratio T

H

and T

L

.

Advertising