3 wiring idec smartrelay, Wiring idec smartrelay, Idec smartrelay installation and wiring – IDEC FL1E SmartRelay User Manual

Page 46: 2 x 1.5 mm, 32 idec smartrelay manual

Advertising
background image

IDEC SmartRelay installation and wiring

32

IDEC SmartRelay Manual

2.3 Wiring IDEC SmartRelay

Wire IDEC SmartRelay using a screwdriver with a 3-mm

blade.
You do not need wire ferrules for the terminals. You can use

conductors with cross-sections of up to the following

thicknesses:
• 1 x 2.5 mm

2

• 2 x 1.5 mm

2

for each second terminal chamber

Tightening torque: 0.4...0.5 Nm or 3...4 in-lbs.

Recommended ferrules
Ferrules order No.

For 1-cable connection

For 2-cable connection

Note

Always cover the terminals after you have completed the
installation. To protect IDEC SmartRelay adequately from
impermissible contact to live parts, comply with local standards.

Cross-section

[mm

2

]

AWG

Phoenix Contact

Ferrule type No.

NIC HIFU

Blade Terminals

type No.

NIC HIFU

Insulated Pin Terminals

type No.

0.3

22

AI0,5-10WH

BT1.25-10-1

0.5

20

AI0,5-10WH

TGN-TC-1.25-11T

0.75

18

AI0,75-8GY

1.25

18

AI1,5-8BK

BT1.25-10-1

BT2-9-1

2.0

16

AI2,5-8BU

BT2-9-1

Recommended

crimping tool

CRIMPFOX ZA 3

NH1

NH61

NH11
NH32
NH65

Cross-section

[mm

2

]

AWG

Phoenix Contact

Ferrule type No.

0.3

22

AI-TWIN2X0,5-8WH

0.5

20

AI-TWIN2X0,5-8WH

0.75

18

AI-TWIN2X0,75-8GY

1.25

18

AI-TWIN2X1,5-8BK

Recommended

crimping tool

CRIMPFOX ZA 3