IDEC FL1E SmartRelay User Manual

Page 176

Advertising
background image

IDEC SmartRelay functions

162

IDEC SmartRelay Manual

Parameters On and Off

The on threshold On and the off threshold Off can be

provided by the actual value of another already-programmed

function. You can use the actual values of the following

functions:

• Analog comparator (actual value Ax - Ay, see Chapter

4.4.18)

• Analog trigger (actual value Ax, see Chapter 4.4.16)

• Analog amplifier (actual value Ax, see Chapter 4.4.20)

• Analog multiplexer (actual value AQ, see Chapter 4.4.26)

• Analog ramp control (actual value AQ, see Chapter

4.4.27)

• Analog math (actual value AQ, see Chapter 4.4.30)

• PI controller (actual value AQ, see Chapter 4.4.28)

• Up/down counter (actual value Cnt, see Chapter 4.4.13)
Select the required function by the block number.

R

Dir

On=Off=5

Cnt

StartVal

Q

Internal count

value Cnt

Timing diagram

Functional description

The internal counter increments (Dir = 0) or decrements (Dir

= 1) by one count with every positive edge at input Cnt.
You can use input R to reset the internal count value to the

start value. As long as R = 1, the output is also 0 and the

pulses at input Cnt are not counted.
If retentivity is not set, output Q and the expired time are

reset after a power failure.
Q is set or reset depending on the current value at Cnt and

the set thresholds. See the calculation rule below.

Calculation rule

• If the On threshold

 Off threshold, then:

Q = 1, if Cnt

 On

Q = 0, if Cnt < Off.

• If the On threshold < Off threshold, then Q = 1,

if On

 Cnt < Off.