IDEC SmartRelay functions

IDEC SmartRelay Manual

187

• When the type of analog outputs is set to 4-20mA:
When internal values less than zero are inputted to the

analog output, the analog output module outputs current

values less than 4mA.

When internal values more than 1000 are inputted to the

analog output, the analog output module outputs 20mA.

The relationship between the internal value Ax inputted to the analog output and
the analog output value:

Note

Using an Analog trigger, you can determine that the internal values
less than zero or more than 1000 are inputted to the analog output.

When the type of analog outputs is set to 4-20mA, and

internal values less than zero are inputted to the analog

output, it outputs current values less than 4mA. You may

need to prevent the analog output module from outputting

current values less than 4mA. To do this, connect the Analog

Multiplexer (B007) in front of the analog output (AQ1) and

connect the Analog trigger (B006) in front of the Analog

Multiplexer to convert the internal values less than zero to

internal values equal to or more than zero.

Analog output value

lnternal value Ax

0

-1000

1000

20mA

4mA

-250