4.4.30 Analog math

Short description

The analog math block calculates the value AQ of an

equation formed from the user-defined operands and

operators.

Symbol in IDEC

SmartRelay

Wiring

Description

Input En

A change in the status from 0 to 1 at
input En (Enable) enables the analog
math function block.

Parameter V1: First operand value

V2: Second operand value

V3: Third operand value

V4: Fourth operand value


Op1: First operator

Op2: Second operator

Op3: Third operator


Pr1: Priority of first operation

Pr2: Priority of second operation

Pr3: Priority of third operation

Qen

0

:

0: Reset value of AQ to 0

when En=0

1: Retain last value of AQ

when En=0

p: Number of decimals

Range of values: 0, 1, 2, 3

Output AQ The output AQ is the result of the

equation formed from the operand
values and operators. AQ will be set
to 32767 if a divide by 0 or overflow
occurs, and -32768 if a negative
overflow (underflow) occurs.