IDEC SmartRelay functions

IDEC SmartRelay Manual

197

Restriction

A maximum of 50 message texts are available.

Functional description

When IDEC SmartRelay is in RUN mode, IDEC SmartRelay

displays the message text that you have configured along

with its parameter values upon a 0 to 1 transition of the signal

at input En.
Based on your setting for the message destination, the

message text displays on the IDEC SmartRelay Display, the

Text Display, or both.
If you use flag M27 in your circuit program, then if M27=0

(low) then IDEC SmartRelay displays the message text only

if it is from the primary character set (Character Set 1). If

M27=1 (high), then IDEC SmartRelay displays the message

text only if is from the secondary character set (Character

Set 2). (See the M27 flag description in section 4.1).
If you have configured message ticking, the message will

tick on and off the display according to your specifications,

either a character at a time, or a line at a time.
If acknowledgment is disabled (Ack = Off), the message text

is hidden when the status of the signal at input En changes

from 1 to 0.
If acknowledgment is enabled (Ack = On) and the status of

the signal at input En changes from 1 to 0, the message text

is output until it is acknowledged with OK. When En = 1, you

cannot acknowledge the message text.
When multiple message text functions are triggered with

En=1, IDEC SmartRelay displays the message text with the

highest priority (0 = lowest, 127 = highest). This also means

that IDEC SmartRelay displays a newly activated message

text only if its priority is higher than that of previously

activated message texts.
After a message text is disabled or acknowledged, the

function automatically shows the previously active message

text that takes the highest priority.
You can change the view and the message texts by pressing