Technical data

300

IDEC SmartRelay Manual

Input current at
• Signal 0
• Signal 1
• Signal 0
• Signal 1

< 0.03 mA AC

> 0.08 mA AC
< 0.03 mA DC
> 0.12 mA DC

Delay time at
• 0 to 1 : 120 V AC

: 240 V AC
: 120 V DC

: 240 V DC

• 1 to 0 : 120 V AC

: 240 V AC

: 120 V DC

: 240 V DC


typ. 50 ms

typ. 30 ms

typ. 25 ms

typ. 15 ms
typ. 65 ms

typ. 105 ms

typ. 95 ms

typ. 125 ms

Line length (unshielded)

100 m

Digital outputs
Number

4

Output type

Relay outputs

Electrical isolation

Yes

Dielectric Strength

(between power/input terminals and
output terminals)

2,500 V AC, 1minute
500 V DC, 1 minute

In groups of

1

Control of a digital input

Yes

Continuous current I

th

max. 10 A per relay

Surge current

max. 30 A

Incandescent lamp load (25000 switching
cycles) at
• 230/240 V AC
• 100/110 V AC


1000 W
500 W

Fluorescent tubes with ballast (25000
switching cycles)

10 x 58 W (at 230/240 V AC)

Fluorescent tubes, conventionally
compensated (25000 switching cycles)

1 x 58 W (at 230/240 V AC)

Fluorescent tubes, uncompensated
(25000 switching cycles)

10 x 58 W (at 230/240 V AC)

Short circuit–proof cos 1

Power protection B16, 600A

Short circuit-proof cos 0.5 to 0.7

Power protection B16, 900A

Derating

none; across the entire temperature range

Parallel output circuits for power increase Not permitted
Protection of output relay (if desired)

max. 16 A, characteristic B16

FL1E-H12RCC

FL1E-B12RCC

Advertising