2 operating states, Operating states – IDEC FL1E SmartRelay User Manual

Page 68

Advertising
background image

IDEC SmartRelay installation and wiring

54

IDEC SmartRelay Manual

4. If you have enabled retentivity for at least one function, or

a function is permanently retentive, the current values are

retained at POWER-OFF.

Note

When a power failure occurs while you are entering a circuit
program, the program in IDEC SmartRelay will be deleted after
power is returned.
Before you modify the circuit program, save a backup copy of your
original to a memory cartridge, a combined memory/battery
cartridge or to a computer (WindLGC).

2.4.2

Operating states

IDEC SmartRelay base module operating states

IDEC SmartRelay base module/Pure knows has two
operating states: STOP and RUN.

Note

After switching the power on, the system briefly switches through
the outputs on the FL1E-H12SND. With an open circuit, a voltage
of > 8 V can occur for up to approximately 100 ms; when loaded,
this time reduces to a matter of microseconds.

STOP

RUN

• The display shows: ’No Program’

(not FL1E-B12...)

• Switching IDEC SmartRelay to

programming mode

(not FL1E-B12...)

• LED is red

(only FL1E-B12...)

• Display: Screen mask for

monitoring I/Os and messages
(after START in the main menu)

(not FL1E-B12...)

• Switching IDEC SmartRelay to

parameter assignment mode

(not FL1E-B12...)

• LED is green

(only FL1E-B12...)

Action of IDEC SmartRelay:
• The input data is not read.
• The circuit program is not

executed.

• The relay contacts are

permanently open or the
transistor outputs are switched
off.

Action of IDEC SmartRelay:
• IDEC SmartRelay reads the

status of the inputs.

• IDEC SmartRelay uses the circuit

program to calculate the status of
the outputs.

• IDEC SmartRelay switches the

relay/transistor outputs on or off.