4.4.13 Up/down counter

Short description

An input pulse increments or decrements an internal value,

depending on the parameter setting. The output is set or

reset when a configured threshold is reached. The direction

of count can be changed with a signal at input Dir.

Symbol in IDEC

SmartRelay

Wiring

Description

Input R

A signal at input R resets the internal
count value to zero.

Input Cnt

The function counts the 0 to 1
transitions at input Cnt. 1 to 0
transitions are not counted.
Use
• inputs I3, I4, I5, and I6 for fast

counting (only FL1E-H12RCE/
FL1E-B12RCE and FL1E-
H12SND): max. 5 kHz.

• any other input or circuit

component for counting low
frequency signals (typ. 4 Hz).

Input Dir

You set the direction of count at input
Dir:
Dir = 0: Up count

Dir = 1: Down count

Parameter

On: On threshold

Range of values:

0...999999

Off: Off threshold

Range of values:

0...999999

StartVal: Initial value from which to
begin counting either down or up.
Retentivity for internal counter value
Cnt:

/ = No retentivity

R = The status is retentive.

Output Q

Q is set or reset, depending on the
current value at Cnt and the set
thresholds.