27 analog ramp control, Analog ramp control – IDEC FL1E SmartRelay User Manual

Page 226

Advertising
background image

IDEC SmartRelay functions

212

IDEC SmartRelay Manual

4.4.27 Analog Ramp Control

Short description

The Analog ramp control instruction allows the output to be

changed from the current level to the selected level at a

specified rate.

Symbol in IDEC

SmartRelay

Wiring

Description

Input En

A change in the status from 0 to 1 at
input En (Enable) applies the start/
stop level (Offset ”B” + StSp) to the
output for 100 ms and starts the ramp
operation to the selected level.

A change in the status from 1 to 0
immediately sets the current level to
Offset ”B”, which makes output AQ
equal to 0.

Input Sel

SeI = 0: Level 1 is selected
SeI = 1: Level 2 is selected
A change in status of Sel causes the
current level to start changing to the
selected level at the specified rate.

Input St

A change in the status from 0 to 1 at
input St (Decelerated Stop) causes
the current level to decrease at a
constant rate until the start/stop level
(Offset ”B” + StSp) is reached. The
start/stop level is maintained for
100ms and then the current level is
set to Offset ”B”, which makes output
AQ equal to 0.