4.4.14 Operating hours counter

Short description

A configured time is triggered with a signal at the monitoring

input. The output is set when this time has expired.

MI = Configured time interval
MN = Time-to-go
OT = Total time expired since the last hi signal at input Ral
These values are always retentive!

Symbol in IDEC

SmartRelay

Wiring

Description

Input R

A positive edge (0 to 1 transition) at

input R resets output Q and sets a

configured value MI at the counter for

the duration of the time-to-go (MN).

Input En

En is the monitoring input. IDEC

SmartRelay scans the on-time of this

input.

Input Ral

A positive edge at input Ral (Reset

all) resets the operating hours

counter (OT) and the output, and sets

the time-to-go value (MN) tothe

maintenance interval MI:

• output Q = 0,

• measured operating time OT = 0

and

• the time-to-go of the maintenance

interval MN = MI.

Parameter

MI : Maintenance interval to be

preset in units of hours and

minutes

Range of values:

0000...9999 h, 0...59 m

OT : The accumulated total operating

time; you can specify an offset in

hours and minutes

Range of values:

00000...99999 h, 0...59 m

Q

0:

• Whenv ”R” is selected:

Q = 1, if MN = 0;

Q = 0, if R = 1 or Ral = 1

• When ”R+En” is selected:

Q = 1, if MN = 0;

Q = 0, if R = 1 or Ral = 1 or En = 0.

Output Q

The output is set when the time-to-go
MN = 0 (see timing diagramm).
The output is reset:
• When ”Q

0:R+En”, if

R = 1 or Ral = 1 or En = 0

• When ”Q

0:R”, if R = 1 or Ral = 1.