5 interval time-delay relay/pulse output, Interval time-delay relay/pulse output – IDEC FL1E SmartRelay User Manual

Page 153

Advertising
background image

IDEC SmartRelay functions

IDEC SmartRelay Manual

139

Functional description

The 0 to 1 signal transition at input Trg triggers the current

time T

a

. Output Q is set when T

a

= T. A further signal at input

Trg does not influence the time T

a

.

The output and the time T

a

are reset with the next 1 signal at

input R.

If retentivity is not set, output Q and the expired time are

reset after a power failure.

4.4.5

Interval time-delay relay/Pulse output

Short description

An input pulse generates a signal with a configurable period

at the output.

Parameter T

Note the information on parameter T in Chapter 4.3.2.

The time for parameter T can be provided by the actual value

of another already-programmed function. You can use the

actual values of the following functions:

• Analog comparator (actual value Ax - Ay, see Chapter

4.4.18)

• Analog trigger (actual value Ax, see Chapter 4.4.16)

• Analog amplifier (actual value Ax, see Chapter 4.4.20)

• Analog multiplexer (actual value AQ, see Chapter 4.4.26)

• Analog ramp control (actual value AQ, see Chapter

4.4.27)

• Analog math (actual value AQ, see Chapter 4.4.30)

• PI controller (actual value AQ, see Chapter 4.4.28)

• Up/down counter (actual value Cnt, see Chapter 4.4.13)

Select the required function by the block number. The

timebase is configurable. For information on valid ranges

and parameter defaults, refer to Chapter 4.4.1.

Symbol in IDEC

SmartRelay

Wiring

Description

Input Trg

A signal at input Trg (Trigger) triggers
the time for the wiping relay function.

Parameter The output is switched off after the

time T has expired (output signal tran-
sition 1 to 0).
Retentivity:

/ = No retentivity

R = The status is retentive.

Output Q

A signal at input Trg sets Q. If the input
signal = 1, output Q remains set for the
time Ta.