Note

Fluctuating analog values are due to screening on the connecting

wire from the analog valuator device to the analog FL1B-J2B2

expansion module (encoder wire) that has either been mounted

incorrectly or not at all.

To avoid fluctuating analog values when using these expansion

modules, proceed as follows:

Use only shielded encoder wires.

Shorten the encoder wire as much as possible. The encoder

wire must not be more than 10 meters long.

Clamp the encoder wire on one side only and clamp it only to

the PE terminal on the FL1B-J2B2 / FL1D-K2B2 / FL1D-K2BM2

expansion module.

Connect ground on the encoder supply to the PE terminal on the

expansion module.