IDEC FL1E SmartRelay User Manual

Page 177

Advertising
background image

IDEC SmartRelay functions

IDEC SmartRelay Manual

163

Note

The system scans the counter limit value cyclically.
Thus, if the pulse frequency at the fast inputs I3, I4, I5 or I6 is faster
than the cycle time, the special function might not switch until after
the specified limit value is exceeded
Example: Up to 100 pulses per cycle can be counted; 900 pulses
have been counted so far. On = 950; Off = 10000. The output is set
in the next cycle, after the value has reached 1000. (The output
would not be set at all if the value Off = 980.)

View in programming mode (example):

B3 1+R
On =001234
Off=000000

B3 1+R
On =123456
Off

B021

or

To set the start value, press or to access the following

screen form:

B3 2+R
STV =0100

If the referenced block (B021, in the example) returns a

value that lies out of the valid range, the value is rounded to

the next valid value.
The view in parameter assignment mode (example):

B3
On =001234
Off=000000
Cnt=000120

B3
On =123456
Off

B021

Cnt=000120

or

Current

cout value