IDEC SmartRelay installation and wiring

IDEC SmartRelay Manual

33

2.3.1

Connecting the power supply

IDEC SmartRelays (FL1E-*12RCC, FL1B-M08C2R2) are

suitable for nominal line voltages of 100 V AC/DC and 240 V

AC/DC. IDEC SmartRelays (FL1E-*12RCA, FL1B-

M08D2R2) are suitable for a supply voltage of 24 V AC/DC.

IDEC SmartRelays (FL1E-H12SND, FL1B-M08B1S2) are

suitable for a supply voltage of 24 V DC. IDEC SmartRelays

(FL1E-*12RCE, FL1B-M08B2R2) are suitable for a supply

voltage of 12 V AC/DC or 24 V AC/DC.

Note the information on connection in the product

information document shipped with your device and the

technical specifications in Appendix A relating to permissible

voltage tolerances, line frequency and current consumption.
The Text Display must be supplied with a voltage of 12 V DC

or 24 V AC/DC.

Note

A power failure might cause an additional edge triggering signal at
the special functions.
The stored data will be from the last uninterrupted cycle.

Connecting IDEC SmartRelay

To connect IDEC SmartRelay to the power supply:

L+

M

M

L+

I1

I2

I3

I4

I5

L1

N

I1

I2

I3

I4

L1

N

IDEC SmartRelay .....

with DC power supply

IDEC SmartRelay .....

with AC power supply

Protection with safety fuse if

required (recommended) for:

FL1E-H12RCE: 0.8 A

FL1E-H12SND: 2.0 A

To suppress surge voltages,

install varistors (MOV) with an

operating voltage at least 20 %

above the rated voltage.

Note

IDEC SmartRelay is a double-insulated switchgear. You do not

need to connect an equipment grounding conductor.