Idec smartrelay installation and wiring – IDEC FL1E SmartRelay User Manual

Page 53

Advertising
background image

M

L+

L+
M

U1 I2 M2 U2

I1 M1

PE

L+

M

M

M

L+

PE terminal for

connecting earth and

shielding the analog

measuring cable

Earth

Cable shielding

DIN rail

PE

RUN/STOP

Current
0...20mA

Reference
Current

Current measurement

Voltage measurement

0-10V

IDEC SmartRelay installation and wiring

IDEC SmartRelay Manual

39

FL1B-J2B2

The illustration above shows an example of four–wire

current measurement and two–wire voltage measurement.

Connecting a two–wire sensor to the FL1B-J2B2
Wire up the two–wire sensor’s connecting wires as follows:
1. Connect the sensor’s output to connection U (0 ... 10 V

voltage measurement) or to connection I (0 ... 20 mA

current measurement) of the FL1B-J2B2 module.

2. Connect the plus connector on the sensor to the 24 V

supply voltage (L+).

3. Connect the ground connection of the current output M

(on the right side of the sensor, as shown in the figure

above) to the corresponding M input (M1 or M2) on the

FL1B-J2B2 module.