IDEC FL1E SmartRelay User Manual

Page 146

Advertising
background image

IDEC SmartRelay functions

132

IDEC SmartRelay Manual

Parameter T

Note the defaults for parameter T in Chapter 4.3.2.
The time for parameter T can also be preset based on the

actual value of another, already-configured function. You

can use the actual values of the following functions:
• Analog comparator (actual value Ax - Ay, see Chapter

4.4.18)

• Analog trigger (actual value Ax, see Chapter 4.4.16)
• Analog amplifier (actual value Ax, see Chapter 4.4.20)
• Analog multiplexer (actual value AQ, see Chapter 4.4.26)
• Analog ramp control (actual value AQ, see Chapter

4.4.27)

• Analog math (actual value AQ, see Chapter 4.4.30)
• PI controller (actual value AQ, see Chapter 4.4.28)
• Counter (actual value Cnt, see Chapter 4.4.13)
Select the required function by the block number. The

timebase is adjustable. Please note the following listing:

Valid ranges of the timebase, if T = parameter

The display in programming mode (example):

B12 +R
T

=04:10h

Valid ranges of the timebase, if T = Actual value of an already-

programmed function

Timebase

max. value

min. resolution

Accuracy

s (seconds)

99:99

10 ms

+ 10 ms

m (minutes)

99:59

1s

+ 1 s

h (hours)

99:59

1 min

+ 1 min

Timebase

max. value

Meaning

Accuracy

ms

99990

Number of ms

+ 10 ms

s

5999

Number of s

+ 1 s

m

5999

Number of min

+ 1 min

Advertising