10 dual-function switch, Dual-function switch, Age 148) – IDEC FL1E SmartRelay User Manual

Page 162

Advertising
background image

IDEC SmartRelay functions

148

IDEC SmartRelay Manual

View in parameter assignment mode (example):

B9 1
T

=60:00s

Ta =06:00s

Current value of T

4.4.10 Dual-function switch

Short description

Switch with two different functions:
• Pulse switch with off-delay
• Switch (permanent lighting)

Symbol in IDEC

SmartRelay

Wiring

Description

Input Trg

A signal at input Trg (Trigger) sets
output Q (permanent light) or resets Q
with an off-delay. When active, output
Q can be reset with a signal at input
Trg.

Input R

A signal at input R resets the current
time T

a

and resets the output.

Parameter T represents the off-delay time. The

output is reset (1 to 0 transition) when
time T expires.
T

L

represents the time during which

the output must be set to enable the
permanent light function.
T

!

represents the on-delay for the

prewarning time.
T

!L

represents the length of the

prewarning time period.
Retentivity:

/ = No retentivity

R = The status is retentive.

Output Q

A signal at Trg switches on output Q.
Depending on the length of the input at
Trg, the output is switched off again or
switched on permanently, or it is reset
with a further signal at Trg.

Advertising