Technical data

IDEC SmartRelay Manual

311

Notice: For fluorescent lamps with capacitors, the technical data of fluorescent lamp
ballasts must also be considered. If the maximum allowed surge current is exceeded,
fluorescent lamps must be switched with appropriate contactor relays.

Fluorescent tubes, uncompensated
(25000 switching cycles)

10 x 58 W

Derating

none; across the entire temperature range

Short circuit-proof cos 1

Power protection B16, 600A

Short circuit-proof cos 0.5 to 0.7

Power protection B16, 900A

Parallel output circuits for power increase Not permitted
Protection of output relay (if desired)

max. 16 A, characteristic B16

Minimum Switching Load

10 mA, 12 V DC

Initial Contact Resistance

100 m

maximum (at 1A, 24V DC)

Mechanical Life

10,000,000 operations minimum

(no load, 10 Hz)

Electrical Life

100,000 operations minimum (rated
resistive load, 1800 operations / hour)

Switching rate
Mechanical

10 Hz

Ohmic load/lamp load

2 Hz

Inductive load

0.5 Hz

FL1E-H12RCA

FL1E-B12RCA