IDEC FL1E SmartRelay User Manual

Page 66

Advertising
background image

IDEC SmartRelay installation and wiring

52

IDEC SmartRelay Manual

Notes for Using Expansion I/O Modules of Version 7 or earlier

When using 3 or more expansion I/O modules including

those of the versions listed below, immediately after power-

up, it takes a specific period of time for the base module to

accept input signals from the expansion I/O modules. Until

the output terminals on the expansion I/O module are actu-

ally turned on or off.

Expansion I/O Modules

FL1B-M08C2R2(Version 1 to 7),

FL1B-M08B1S2(Version 1 to 7),

FL1B-M08B2R2(Version 1 to 7),

FL1B-M08D2R2(Version 1 to 7),

FL1B-J2B2(Version 1 to 7),

FL1D-K2B2(Version 1)
For identifying the version, see page 5.

10sec

Power supply

External input signal to base module and expansion modules

I/O signal of base module is reflected

FB process

During the initialization of expansion modules

The initialization period

of base module

I/O signal of expansion modules

I/O signal of expansion modules is reflected

in the user program.

*1

is reflected

.

in the user program.

*1

Version 7 or earlier

*2

Version 8 or later

*1 Output signal of base module and expansion modules

are reflected 1 scan time after each input signal has been re-

flected.
*2 During the initialization period of expansion I/O modules,

inputs and outputs are off. In addition, the length of initializa-

tion period varies with expansion I/O modules , and I/O re-

sponse depends on the expansion I/O modules.
For further information, see our Internet address

(URL: http://www.idec.com/faq/en/controller/).