IDEC FL1E SmartRelay User Manual

Page 173

Advertising
background image

IDEC SmartRelay functions

IDEC SmartRelay Manual

159

Example 8: Yearly mode on, Monthly mode on, On Time =

2008

**

01, Off Time = 2010

**

05: Starting in 2008, on the

first day of each month the timer output switches on and

switches off on the fifth day of the month. The timer

continues in this pattern through the last month of 2010.

B6 2+
ON :
YYYY–MM–DD
2008–**–01

B6 1+
Yearly =On
Monthly=On
Pulse =Off

B6 3+
OFF :
YYYY–MM–DD
2010–**–05

Functional description

The twelve-month time switch sets and resets the output at

specific on and off dates. Sets and resets are executed at

00:00. If your application requires a different time, use a

seven-day time switch together with a twelve-month time

switch in your circuit program.

The on time specifies when the timer is activated. The off

time specifies when the output is reset again. For the on and

off times, note the order of the fields: The first field defines

the year, the second the month and the third the day.

If you set the Monthly mode on, the timer output switches on

each month at the specified day of the on time and remains

on until the specified day of the off time. The on time

specifies the initial year in which the timer is activated. The

off time defines the last year in which the timer turns off. The

maximum year is 2099.

If you set the Yearly mode on, the timer output switches on

each year at the specified month and day of the on time and

remains on until the specified month and day of the off time.

The on time specifies the initial year in which the timer is

activated. The off time defines the last year in which the timer

turns off. The maximum year is 2099.

If you set Pulse output, the timer output switches on at the

specified on time for one cycle and then the timer output is

reset. You can choose to pulse a timer on a monthly or yearly

basis, or just a single time.

If you set none of the Monthly, Yearly, or Pulse modes on,

you can define a specific time period with the on time and off

time. It can span any time period that you choose.

For a process action that is to be switched on and off at

multiple but irregular times during the year, you can define

multiple twelve-month time switches with the outputs

connected by an OR function block.