15 frequency trigger, Frequency trigger – IDEC FL1E SmartRelay User Manual

Page 182

Advertising
background image

IDEC SmartRelay functions

168

IDEC SmartRelay Manual

4.4.15 Frequency trigger

Short description

The output is set and reset with two configurable frequency

triggers.

Parameter G_T

The gate time G_T can be provided by the actual value of

another already-programmed function. You can use the

actual values of the following functions:

• Analog comparator (actual value Ax - Ay, see Chapter

4.4.18)

• Analog trigger (actual value Ax, see Chapter 4.4.16)

• Analog amplifier (actual value Ax, see Chapter 4.4.20)

• Analog multiplexer (actual value AQ, see Chapter 4.4.26)

• Analog ramp control (actual value AQ, see Chapter

4.4.27)

• Analog math (actual value AQ, see Chapter 4.4.30)

• PI controller (actual value AQ, see Chapter 4.4.28)

• Up/down counter (actual value Cnt, see Chapter 4.4.13)
Select the required function by the block number.

Symbol in IDEC

SmartRelay

Wiring

Description

Input Fre

The function counts the 0 to 1
transitions at input Fre. 1 to 0
transitions are not counted.
Use
• inputs I3, I4, I5, I6 for fast counting

(only FL1E-H12RCE/FL1E-
B12RCE and FL1E-H12SND): max.
5 kHz.

• any other input or circuit component

for counting low frequency signals
(typ. 4 Hz).

Parameter On : On threshold

Range of values:

0000...9999

Off : Off threshold

Range of values:

0000...9999

G_T : Time interval or gate time during

which the input pulses are
measured.

Range of values:

00:05 s...99:99 s

Output Q

Q is set and reset at the thresholds.

Fre

Advertising