25 shift register, Shift register – IDEC FL1E SmartRelay User Manual

Page 222

Advertising
background image

IDEC SmartRelay functions

208

IDEC SmartRelay Manual

4.4.25 Shift register

Short description

You can use the shift register function to read the value of an

input and to shift its bits left or right. The output value

corresponds with the configured shift register bit. The

shifting direction can be changed at a special input.

Functional description

The function reads the value at input In with a positive edge

(0 to 1 transition) at input Trg (Trigger).
This value is applied to shift register bit S1 or S8, depending

on the shifting direction:

• Shift up: The value at input In is set at S1; the previous

value at S1 is shifted to S2; the previous value at S2 is

shifted to S3 etc.

• Shift down: The value at input In is set at S8; the previous

value at S8 is shifted to S7; the previous value at S7 is

shifted to S6 etc.

Output Q returns the value of the configured shift register bit.
If retentivity is disabled, the shift function restarts at S1 or S8

after a power failure. When enabled, retentivity always

applies to all shift register bits.

Note

The special function shift register can be used only once in the cir-

cuit program.

Symbol in IDEC

SmartRelay

Wiring

Description

Input In

Input read at the start of the function.

Input Trg

A positive edge (0 to 1 transition) at

input Trg (Trigger) starts the special

function. 1 to 0 transitions are

irrelevant.

Input Dir

The signal at input Dir determines the

shifting direction for the shift register

bits S1...S8:

Dir = 0: Shift up (S1 >> S8)

Dir = 1: Shift down (S8 >> S1)

Parameter Shift register bit that determines the

value at output Q.

Possible settings: S1 ... S8

Retentivity:

/ = No retentivity

R = The status is retentive.

Output Q

The output value corresponds with the

configured shift register bit.